A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Machine room light bulbs and/or ballast need replacement.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Expired
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Provide machine room light. See 2019 report.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Expired
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Remove all non elevator related items/equipment from elevator machine room. See 2017 report.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
Provide unobstructed path to elevator machine room. See 2019 report.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door to be self closing and self locking type.
|
|
conversion
|
conversion
|
n/a
|
|
|
Cannot use machine room for storage
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
|
|
Machine room lighting shall be 10ft candles or greater.
|
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
101.3a
|
|
|
Access to machine room shall be unobstructed.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
None
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
Unsealed
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Remove sheet metal from top of Hoistway.. if roof still leaks, repair roof.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current certificate.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Remove attached sheet metal, top of hoistway being used as drain, repair roof if needed.SECOND NOTICE.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door to be self closing and self locking. SECOND NOTICE.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Remove all non elevator related items from the elevator machine room. SECOND NOTICE.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Remove stored items from machine room, only elevator related materials can be kept in elevator machine room.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Provide self locking, self closing elevator machine room door
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in elevator cab does not work. Re-inspection required
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current operating certificate shall be displayed in machine room.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Emergency phone not working - reinspect
|
9/21/2018
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall work.
|
3/31/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
2/15/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Operator unable to provide location, repair as needed.
|
10/6/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone not working correctly.
|
11/3/2023
|