MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
2nd floor smoke detector sends car to floor #1 needs to go to floor #3
|
3/15/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Need testign procedures in the MCP in the machine room
|
|
A17.1-2016 : Elevators
|
6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980)
|
8.6.11.1 Firefighters’ Emergency Operation
|
|
|
PERFORM MONTHLY FIRE SERVICE TEST AND CODUMENT ON THE LOG POSTED IN MACHINE ROOM
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
POST CURRENT STATE CERTIFICATE IN THE MACHINE ROOM
|
|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.11.10.3
|
|
|
REPLACE MISSING SECTION OF CARPET AT 2ND FLOOR ENTRANCE - TRIPPING HAZARD
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
When smoke detector recall was tested the second floor smoke recalls to the lower level. It needs to go up to the third level. When smoke detector recall tested there was no lit, fire hat, or buzzer in the car
|
4/21/2025
|