A17.1-2016 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
2.1.5
|
x
|
|
All ledges greater than 4"shall be properly gaurded and/or beveled at 70deg.
|
|
|
A17.1-2016 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
2.1.6
|
x
|
|
Walkway at top of hoistway shall have proper standard handrail w/toekick or 70deg bevel installed.
|
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.1.1
|
x
|
|
Upper machine level guardrail is only 32" in height. shall be standard height (42") with midrail (21") and toe kick in the machine room.
|
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
Upper machine level lighting shall not be less than 19ftc in the machine room.
|
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.10.2.2.1(q)
|
x
|
|
Test emergency power.
|
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.10.2.2.2(r)
|
x
|
|
Disconnects shall be labeled with location feeder breakers and function in the machine room.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Door closing exceeds 30 pounds needs adjsuting
|
6/14/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light in car not working
|
6/14/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Repair emergency light
|
11/21/2025
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state certificate in machine room
|
11/21/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need all CAT5 test items performed except POPY nad Gov spin, Fire service 1&2, finals, ETS, NTS, and items found on 17.2 list.
|
1/27/2026
|
|
A17.1-2016 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
2.1.5
|
x
|
|
All ledges greater than 4"shall be properly gaurded and/or beveled at 70deg.
|
1/27/2026
|
|
A17.1-2016 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
2.1.6
|
x
|
|
Walkway at top of hoistway shall have proper standard handrail w/toekick or 70deg bevel installed.
|
1/27/2026
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.1.1
|
x
|
|
Upper machine level guardrail is only 32" in height. shall be standard height (42") with midrail (21") and toe kick in the machine room.
|
1/27/2026
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
Upper machine level lighting shall not be less than 19ftc in the machine room.
|
1/27/2026
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.10.2.2.1(q)
|
x
|
|
Test emergency power.
|
1/27/2026
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.10.2.2.2(r)
|
x
|
|
Disconnects shall be labeled with location feeder breakers and function in the machine room.
|
1/27/2026
|
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.3.2 (Re-Inspection)
|
x
|
|
Ropes appear to be rubbing top of hoistway spinkler pipe. Check and take corrective action.
|
1/27/2026
|
|
A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13 Door Systems
|
x
|
|
Adjust 2nd floor hoistway door upthrust rollers for proper clearance. (lower gap>1")
|
1/27/2026
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
FAID recall not working properly
|
1/27/2026
|