Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 11/21/2025
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) Yes No Ropes appear to be rubbing top of hoistway spinkler pipe. Check and take corrective action. 1/27/2026
A17.1-2016 : Elevators 4.2 - Hoistway doors 8.6.4.13 Door Systems Yes No Adjust 2nd floor hoistway door upthrust rollers for proper clearance. (lower gap>1") 1/27/2026
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 Yes No FAID recall not working properly 1/27/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need all CAT5 test items performed except POPY nad Gov spin, Fire service 1&2, finals, ETS, NTS, and items found on 17.2 list. 1/27/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) Yes No Test emergency power. 1/27/2026
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 Yes No Upper machine level guardrail is only 32" in height. shall be standard height (42") with midrail (21") and toe kick in the machine room. 1/27/2026
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 Yes No Upper machine level lighting shall not be less than 19ftc in the machine room. 1/27/2026
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.10.2.2.2(r) Yes No Disconnects shall be labeled with location feeder breakers and function in the machine room. 1/27/2026
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.5 Yes No All ledges greater than 4"shall be properly gaurded and/or beveled at 70deg. 1/27/2026
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 Yes No Walkway at top of hoistway shall have proper standard handrail w/toekick or 70deg bevel installed. 1/27/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) Yes No Test emergency power.
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 Yes No Upper machine level guardrail is only 32" in height. shall be standard height (42") with midrail (21") and toe kick in the machine room.
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 Yes No Upper machine level lighting shall not be less than 19ftc in the machine room.
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.10.2.2.2(r) Yes No Disconnects shall be labeled with location feeder breakers and function in the machine room.
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.5 Yes No All ledges greater than 4"shall be properly gaurded and/or beveled at 70deg.
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 Yes No Walkway at top of hoistway shall have proper standard handrail w/toekick or 70deg bevel installed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No Door closing exceeds 30 pounds needs adjsuting 6/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency light in car not working 6/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Repair emergency light 11/21/2025