Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x FAID recall not working properly 1/27/2026
A17.1-2016 : Elevators 4.2 - Hoistway doors 8.6.4.13 Door Systems x Adjust 2nd floor hoistway door upthrust rollers for proper clearance. (lower gap>1") 1/27/2026
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) x Ropes appear to be rubbing top of hoistway spinkler pipe. Check and take corrective action. 1/27/2026
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.10.2.2.2(r) x Disconnects shall be labeled with location feeder breakers and function in the machine room. 1/27/2026
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.10.2.2.2(r) x Disconnects shall be labeled with location feeder breakers and function in the machine room.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) x Test emergency power. 1/27/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) x Test emergency power.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 11/21/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x Upper machine level lighting shall not be less than 19ftc in the machine room. 1/27/2026
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x Upper machine level lighting shall not be less than 19ftc in the machine room.
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 x Upper machine level guardrail is only 32" in height. shall be standard height (42") with midrail (21") and toe kick in the machine room. 1/27/2026
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 x Upper machine level guardrail is only 32" in height. shall be standard height (42") with midrail (21") and toe kick in the machine room.
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 x Walkway at top of hoistway shall have proper standard handrail w/toekick or 70deg bevel installed. 1/27/2026
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 x Walkway at top of hoistway shall have proper standard handrail w/toekick or 70deg bevel installed.
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.5 x All ledges greater than 4"shall be properly gaurded and/or beveled at 70deg. 1/27/2026
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.5 x All ledges greater than 4"shall be properly gaurded and/or beveled at 70deg.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Repair emergency light 11/21/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light in car not working 6/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Door closing exceeds 30 pounds needs adjsuting 6/14/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need all CAT5 test items performed except POPY nad Gov spin, Fire service 1&2, finals, ETS, NTS, and items found on 17.2 list. 1/27/2026