MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
Yes
|
No
|
Emergency light shall be operational.
|
4/14/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency bell shall be operational.
|
4/14/2026
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
No
|
No
|
Test phase 2 fire service
|
3/25/2026
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Post current state certificate in machine room
|
3/25/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
Yes
|
No
|
Repair emergency lights
|
7/30/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
Yes
|
No
|
Repair car door close button
|
7/30/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
Yes
|
No
|
Emergency light in car not working
|
6/27/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
Yes
|
No
|
Door closing over 30 pounds needs adjusting
|
6/27/2022
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
Yes
|
No
|
Upper machine level lighting shall not be less than 19fc.
|
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
Emergency power shall be tested.
|
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.8.1
|
Yes
|
No
|
-Disconnects shall be labeled with location of feeder breakers and function.
|
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.3
|
Yes
|
No
|
Upper machine level guardrail is only 32" in height. Shall be standard height(42") with midrail (21") and toe kick.
|
|
|
A17.1-2016 : Elevators
|
3.11 - Hoistway smoke control
|
2.1.4
|
Yes
|
No
|
All ledges greater than 4" shall be properly guarded and/or beveled at 70deg.
|
|
|
A17.1-2016 : Elevators
|
3.11 - Hoistway smoke control
|
2.1.4
|
Yes
|
No
|
Walkway at top of hoistway shall have proper Standard Handrail w/toekick or 70deg Bevel installed.
|
|