Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State certificate in machine room 12/21/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Yes No The pit light shall illuminate when switched on.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Yes No Insufficient illumination in the elevator machine room. Machine room shall maintain a minimum of 10 foot candles at floor level.
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Machine room walls shall not contain holes.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Repair hole cut into the machine room wall. (2nd Notice) 3/25/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No A code compliant MCP and related on-site documentation shall be provided in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Need a maintenance control program on site posted on controller 3/25/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) No No Need testing procedures in the MCP on or before 1/1/22 3/25/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency light not working 4/15/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Repair hole cut into the machine room wall 3/25/2026