MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Post current State certificate in machine room
|
12/21/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
No
|
No
|
Need a maintenance control program on site posted on controller
|
3/25/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests)
|
No
|
No
|
Need testing procedures in the MCP on or before 1/1/22
|
3/25/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
Yes
|
No
|
Emergency light not working
|
4/15/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
No
|
No
|
Repair hole cut into the machine room wall
|
3/25/2026
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
No
|
No
|
Repair hole cut into the machine room wall. (2nd Notice)
|
3/25/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
No
|
No
|
A code compliant MCP and related on-site documentation shall be provided in the machine room.
|
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
Yes
|
No
|
The pit light shall illuminate when switched on.
|
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
Yes
|
No
|
Insufficient illumination in the elevator machine room. Machine room shall maintain a minimum of 10 foot candles at floor level.
|
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
No
|
No
|
Machine room walls shall not contain holes.
|
|