Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed and needs full load test on or before next inspection. 9/28/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be kept on site for each elevator. 9/28/2022
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 9/28/2022
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed as noted in the last inspection. Perform required testing, seal & tag within 90 days. Re-inspection required 9/27/2022