A17.1-2016 : Elevators
|
3.2 - Car top light and outlet
|
8.10.2.2.3(b)
|
|
|
The car top light shall be operational
|
|
|
A17.1-2016 : Elevators
|
3.2 - Car top light and outlet
|
8.10.2.2.3(b)
|
|
|
The electrical fitting on the car-top emergency exit switch is broken and shall be repaired or replaced.
|
|
|
A17.1-2016 : Elevators
|
6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980)
|
8.6.11.1 Firefighters’ Emergency Operation
|
|
|
Firefighters phase one instructions shall be posted near the phase one keyswitch in the hallway at the egress floor.
|
|
|
conversion
|
conversion
|
n/a
|
|
|
Compensating chains needs to be shortened.
|
6/12/2019
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
The MCP is missing the evacuation procedures. (This item is for notification purposes for future violation in 2022)
|
7/30/2021
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
x
|
Red tag issued: damaged hoistway ropes. Replace ropes and check driver for damaged grooves.
|
9/5/2024
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Fire service operation shall be tested.
|
9/5/2024
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Need to perform brake, buffer, car & counterweight, safety slide testing.
|
8/1/2019
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current Mo state operating certificate ahll be posted in the elevator equipment room in a noncombustible frame with a clear protective vision place over it.
|
|