Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current Mo state operating certificate ahll be posted in the elevator equipment room in a noncombustible frame with a clear protective vision place over it.
A17.1-2016 : Elevators 3.2 - Car top light and outlet 8.10.2.2.3(b) The car top light shall be operational
A17.1-2016 : Elevators 3.2 - Car top light and outlet 8.10.2.2.3(b) The electrical fitting on the car-top emergency exit switch is broken and shall be repaired or replaced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records The MCP is missing the evacuation procedures. (This item is for notification purposes for future violation in 2022) 7/30/2021
A17.1-2016 : Elevators 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) 8.6.11.1 Firefighters’ Emergency Operation Firefighters phase one instructions shall be posted near the phase one keyswitch in the hallway at the egress floor.
conversion conversion n/a Compensating chains needs to be shortened. 6/12/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Need to perform brake, buffer, car & counterweight, safety slide testing. 8/1/2019
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x x Red tag issued: damaged hoistway ropes. Replace ropes and check driver for damaged grooves. 9/5/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Fire service operation shall be tested. 9/5/2024