Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) The MCP is missing the evacuation procedures. (This item is for notification purposes for future violation in 2022) 7/30/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Top emergency exit shall be properly secured. The bolts are damaged.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Hoist ropes showing signs of flattening and reduction in diameter. Currently measures "go". Ropes should be replaced before next annual test and check driver for damaged grooves.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Fire service operation must be tested.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Need to perform brake, buffer, car & counterweight, safety slide and fireman's recall/operation testing. 8/1/2019