Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Top emergency exit shall be properly secured. The bolts are damaged.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Hoist ropes showing signs of flattening and reduction in diameter. Currently measures "go". Ropes should be replaced before next annual test and check driver for damaged grooves.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Hoist ropes have some flattening on them but still measure "go". Ropes should be monitored for further wear.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Traveling cable strain device under car is broken and needs replacement.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) MCP shall be current including fire service test log.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current state operating certificate shall be displayed in machine room in non-combustible frame.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency power operations shall be tested.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Need to perform brake, buffer, car & counterweight, safety slide and fireman's recall/operation testing. 8/1/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) The MCP is missing the evacuation procedures. (This item is for notification purposes for future violation in 2022) 7/30/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Fire service operation must be tested. 6/12/2025