MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Need to perform brake, buffer, car & counterweight, safety slide and fireman's recall/operation testing.
|
8/1/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Fire service operation must be tested.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning)
|
|
|
The MCP is missing the evacuation procedures. (This item is for notification purposes for future violation in 2022)
|
7/30/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Top emergency exit shall be properly secured. The bolts are damaged.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Hoist ropes showing signs of flattening and reduction in diameter. Currently measures "go". Ropes should be replaced before next annual test and check driver for damaged grooves.
|
|