Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Alarm bell shall work with loss of main 120v power. 6/12/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Alarm bell shall work with loss of 120v power. (2nd Notice) To be corrected and re-inspected immediately or unit to be red tagged out of service. 6/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Strain device is missing from traveling cable under car.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) MCP shall be current including fire service test log.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x The door closing force shall not be more than 30 lbs. 10/2/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) The MCP is missing the evacuation procedures. (This item is for notification purposes for future violation in 2022) 7/30/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Top emergency exit shall be properly secured. The bolts are damaged.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Alarm bell shall work with loss of 120v power. (2nd Notice) To be corrected and re-inspected immediately or unit to be red tagged out of service.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x x The hoist ropes are undersized and shall be replaced. (Found at floors 10 & 12). Elevator Red Tagged. 4/15/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Fire service operation shall be tested. 6/12/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency power operation must be tested. 6/14/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current state operating certificate shall be displayed in machine room in non-combustible frame.