MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm bell shall work with loss of main 120v power.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Fire service operation shall be tested.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Top emergency exit shall be properly secured. The bolts are damaged.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
x
|
|
The door closing force shall not be more than 30 lbs.
|
10/2/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning)
|
|
|
The MCP is missing the evacuation procedures. (This item is for notification purposes for future violation in 2022)
|
7/30/2021
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
x
|
The hoist ropes are undersized and shall be replaced. (Found at floors 10 & 12). Elevator Red Tagged.
|
4/15/2024
|