Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Yes No The door closing force shall not be more than 30 lbs. 10/2/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) No No The MCP is missing the evacuation procedures. (This item is for notification purposes for future violation in 2022) 7/30/2021
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes Yes The hoist ropes are undersized and shall be replaced. (Found at floors 10 & 12). Elevator Red Tagged. 4/15/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Alarm bell shall work with loss of main 120v power. 6/12/2025
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Fire service operation shall be tested. 6/12/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Top emergency exit shall be properly secured. The bolts are damaged. 9/26/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Alarm bell shall work with loss of 120v power. (2nd Notice) To be corrected and re-inspected immediately or unit to be red tagged out of service. 6/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Strain device is missing from traveling cable under car. 9/26/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No MCP shall be current including fire service test log. 9/26/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current state operating certificate shall be displayed in machine room in non-combustible frame. 9/26/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Emergency power operation must be tested. 6/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Alarm bell shall work with loss of 120v power. (2nd Notice) To be corrected and re-inspected immediately or unit to be red tagged out of service. 10/23/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes No Suspension ropes shall be shorteded.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Yes No Machine room floors, machinery, and control spaces shall be kept free of water, dirt, rubbish, oil, and grease.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes No Horizontally sliding or single0section swing doors of automatic operation elevators shall be provided with door closers arranged to close an open door automaticlly if the car, for any reason, leaves the landing zone.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency bell does not work.