Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes Yes Re-inspection of drive machine brake, unit will not run (keeps tripping overload) Could not test brake, elevator still Red-tagged, Re-inspection required 10/12/2022
MO Minimum : Elevators (D) - Brakes (D)1 Yes Yes Traction machine brake hub is off center causing vibration and brake to overheat, need to replace brake. Red-tagged, removed from service. Re-inspection required 10/5/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No Yes Traction driving machine will not pick rated load due to suspension ropes loosing traction on machine sheave. Red tagged, removed from service. Re-inspection required 9/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Replace seals on traction driving machine, leaking fluid.
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)8 Yes Yes Test car safeties with rated load at rated speed. Red tagged, Re-inspection required 9/28/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be on display in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No A copy of the MCP shall be kept in the machine room for each elevator
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No A copy of the MCP shall be kept in the machine room for each unit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) Yes No Hoist ropes shall be shortened, the counterweight is touching the springs when the car is at the top floor. Re-inspection required within 30 days 9/1/2023