Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)1 Tighten bottom floor hoistway door gibs. 12/5/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)6 x Door safety edge is not working.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x Replace any missing/damaged panels, buttons, or spacer on the COP.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x A17.1 ITEM 1.6 CAR EMERGENCY SIGNAL: ALARM BELL NOT WORKING 2/19/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Evacuation procedures are missing from the MCP.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Empty oil filled drip pan under machine and/or repair leak. 12/5/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Alarm bell does not work. 6/6/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car door restrictor does not work. 6/6/2022
MO Minimum : Elevators (I) - Pits (I)1 Clean trash from elevator pit. 12/5/2023
MO Minimum : Elevators (I) - Pits (I)1 Clean pit. 12/5/2023
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept clean and dry.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Fire service testing log is missing from the MCP.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Relief valve and fire service shall be tested.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.4 Plunger Gripper Testing OSV is sealed but does not have a tag on it. Must perform a category 5 weight test on the OSC within 90 days 10/24/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 11/30/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Place current state operating certificate in machine room. 12/5/2023