MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
No
|
No
|
Replace cylinder gland packing seal.
|
5/18/2021
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
6/5/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning)
|
No
|
No
|
Evacuation procedures missing from the MCP.
|
6/5/2026
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
No
|
No
|
Fire service testing log is missing from the MCP.
|
6/5/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
Yes
|
No
|
Door restrictor shall be operational.
|
6/5/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
Yes
|
No
|
Door restrictor shall be repaired to prevent door from opening more than 4" when not at a landing.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
Yes
|
No
|
Emergency Light not working and shall be repaired
|
|