Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Need maintenance control program on site posted on controller 3/12/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current Mo certificate in machine room 3/12/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Counterweight runby was 31/2 inches. Ropes need to be shortened 9/25/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Counterweight runby was 3 1/2 inches. Ropes need to be shortened. (2nd Notice) 30 days maximum to correct violation or unit will be red tagged and locked out of service for non-compliance. 12/12/2024