Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Operation of elevators equipped with standby or emergency power shall be tested to determine conformance with the applicable requirements. Tests shall be performed with no load in the car. 11/4/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Operation of elevators equipped with standby or emergency power shall be tested to determine conformance with the applicable requirements. Tests shall be performed with no load in the car. 8/3/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No Adjust upthrust roller bearings for proper clearance to door hanger track (2nd landing).
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No Adjust upthrust roller bearings for proper clearance to door hanger track (2nd landing).
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No Replace missing fire tab on hoistway door at second landing.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No Replace missing fire tab on hoistway door at second landing. 8/22/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 7/11/2024
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b No No Provide machine room ventilation. 11/7/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) No No Clean the pit. 11/7/2019
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) No No Clean the car top. 11/7/2019
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Emergency power indicator light (located in boiler room lobby) is damaged. Repair or replace as needed. 12/23/2019
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. (Repeat Violation) 8/22/2024
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal Yes No The elevator has an emergency power indicator light that does not illuminate when the car is running on emergency power - this shall be corrected.
A17.1-1996 : Elevators 3.9 - Floor and emergency identification numbering 211.9 No No Provide car numbering on car top. 11/7/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 11/6/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 10/17/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A completed fire service log shall be kept on-site. 11/7/2019
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.1.7 Yes No 8.6.1.7.5 - Emergency lowering device (ERU) shall be operational. 11/4/2020
conversion conversion n/a No No Need copy of current state operating certificate in machine room. 10/4/2018