Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Operation of elevators equipped with standby or emergency power shall be tested to determine conformance with the applicable requirements. Tests shall be performed with no load in the car. 11/4/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Operation of elevators equipped with standby or emergency power shall be tested to determine conformance with the applicable requirements. Tests shall be performed with no load in the car. 8/3/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Adjust upthrust roller bearings for proper clearance to door hanger track (2nd landing).
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Adjust upthrust roller bearings for proper clearance to door hanger track (2nd landing).
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Replace missing fire tab on hoistway door at second landing.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Replace missing fire tab on hoistway door at second landing. 8/22/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 7/11/2024
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b Provide machine room ventilation. 11/7/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) Clean the pit. 11/7/2019
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) Clean the car top. 11/7/2019
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Emergency power indicator light (located in boiler room lobby) is damaged. Repair or replace as needed. 12/23/2019
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. (Repeat Violation) 8/22/2024
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal x The elevator has an emergency power indicator light that does not illuminate when the car is running on emergency power - this shall be corrected.
A17.1-1996 : Elevators 3.9 - Floor and emergency identification numbering 211.9 Provide car numbering on car top. 11/7/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 11/6/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 10/17/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A completed fire service log shall be kept on-site. 11/7/2019
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.1.7 x 8.6.1.7.5 - Emergency lowering device (ERU) shall be operational. 11/4/2020
conversion conversion n/a Need copy of current state operating certificate in machine room. 10/4/2018