Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)17 Yes No There is a sprinkler riser that runs the full length of the hoistway. Take corrective action as needed or apply for a variance. 6/22/2026
MO Minimum : Elevators (A) - Hoistways (A)17 Yes No There is a sprinkler riser that runs the full length of the hoistway. Take corrective action as needed or apply for a variance.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No 8.6.1.7.5 - The emergency lowering device (ERU) shall be operational. 10/9/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No The MCP is missing. 10/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 10/14/2025
MO Minimum : Elevators (I) - Pits (I)1 No No The pit must be clean and free of oil and debris. 10/14/2025
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No A completed fire service testing log shall be kept on-site. 10/9/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 10/14/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 12/28/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) Yes No The overspeed valve is not tagged or sealed. Category 5 testing is overdue. Unit to be red tagged if not completed within 90 days. 9/9/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Emergency power must be tested annually. (2nd Notice) 9/9/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) Yes No The overspeed valve is not tagged or sealed. Category 5 testing is overdue. Unit to be red tagged if not completed within 90 days. 10/14/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Battery lowering function shall be operational. Repair and test or apply for State variance. 6/22/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator, annually. Last tested 9/9/24. 6/22/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No 8.6.4.19.7 - Operation of elevators equipped with standby or emergency power shall be tested to determine conformance with the applicable requirements. Tests shall be performed with no load in the car. 11/4/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No 8.6.4.19.7 - Operation of elevators equipped with standby or emergency power shall be tested to determine conformance with the applicable requirements. Tests shall be performed with no load in the car. 12/8/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator, annually
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) No No Provide car numbering on the controller. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) No No Provide car numbering on disconnect(s). 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) No No Provide car numbering on car top. 10/9/2020
conversion conversion n/a No No Need copy of current state operating certificate in machine room. 10/4/2018
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 10/9/2020