Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)12 x Override the car call floor lockout switches on Phase 2 fire service. 11/8/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room. 4/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 4/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Cab handrails shall be properly fastened. 4/16/2021