MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
x
|
Fire initiating devices have been installed but need to be tested with an inspector present.
|
6/16/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone dials out but does not connect.
|
6/22/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Remove non-elevator related material from machine room. (Gallons of paint-water hose-water sprinkler-snow shovel)
|
6/20/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Water accumulated in the elevator pit from the broken water line from the drinking fountain shall be removed.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Install smoke sensing devices at elevator lobbies except the main designated landing. The smoke sensing devices, when activated, shall return elevator to the main designated landing.
|
6/13/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Remove newly installed fire initiating device at the main landing. Per A17.1-1978 rule 211.3a2
|
6/16/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
|
|
No audible signal during fire recall
|
6/20/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed
|
6/20/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams)
|
|
|
Keep up to date wiring diagrams in the machine room. The wiring diagrams on site are not the correct ones for the elevator.
|
6/1/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams)
|
|
|
Keep the correct and up to date wiring diagrams for the elevator in the machine room.
|
6/20/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.11.1 Firefighters' Emergency Operation & Documentation
|
|
|
Test and log firefighter operation monthly
|
6/1/2022
|