MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
No lights in machine room, need to install adequate lighting
|
|
conversion
|
conversion
|
n/a
|
|
|
non elevator stuff stored in machine room, also blocking access to main line disconnect
|
11/20/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Need "IN Case of Fire" signs by each Hall call button.
|
12/1/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Non-elevator STUFF can not be stored in Elevator Equipment room
|
12/1/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces
|
|
|
No storage allowed in Elevator equipment room
|
12/20/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
TKE needs to supply maintenance records
|
12/20/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Need to have In Case of Fire signs by each Hall call button
|
12/20/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
Machine room needs to be reachable in a clear and unobstructed manner
|
12/20/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machin rooms shall be provided with at least 10 foot candles of lighting
|
12/20/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher in Elevator machine room not checked since 2019
|
12/20/2021
|