Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a No No non elevator stuff stored in machine room, also blocking access to main line disconnect 11/20/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Need "IN Case of Fire" signs by each Hall call button. 12/1/2020
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Non-elevator STUFF can not be stored in Elevator Equipment room 12/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces No No No storage allowed in Elevator equipment room 12/20/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No TKE needs to supply maintenance records 12/20/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Need to have In Case of Fire signs by each Hall call button 12/20/2021
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No Machine room needs to be reachable in a clear and unobstructed manner 12/20/2021
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Machin rooms shall be provided with at least 10 foot candles of lighting 12/20/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher in Elevator machine room not checked since 2019 12/20/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No No lights in machine room, need to install adequate lighting 10/5/2025
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No No lights in machine room, need to install adequate lighting
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No MUST HAVE CURRENT TEST TAG ON FIRE EXTINGUISHERS