A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Testing Incomplete. All testing requiring weights remain.
|
7/31/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.9 - Buffers and emergency terminal speed limiting devices
|
2.26.2.22
|
x
|
|
Traveling buffer assembly roller is worn out. Replace roller.
|
2/10/2020
|