A17.1-2016 : Elevators
|
2.29 - Car and counterweight safeties
|
8.6.4.19.2
|
Yes
|
Yes
|
winding drum safeties had over 6ft of pull out to set safeties 42 ins is allowed
|
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
No
|
No
|
provide a safe means of access to an from the roof to get to the machroom what is ther is very dangerous.
|
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
No
|
No
|
machine room door not self closing or self locking provide fire rated self locking an self closing door
|
|
|
A17.1-1996 : Elevators
|
3.9 - Floor and emergency identification numbering
|
211.9
|
No
|
No
|
Identify the inside of hoistway doors with a numeral
|
9/8/2023
|
|
A17.1-1996 : Elevators
|
3.27 - Crosshead data plate
|
207.3
|
No
|
No
|
Crosshead data tag needs to specify capacity of 1500#
|
9/8/2023
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
No
|
No
|
Steps to machine room deteriorating, repair as necessary.
|
10/5/2024
|