Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Elevators connected to an emergency or standby generator shall be tested for operation on emergency power. Emergency power test failed, generator would not start. Re-inspection required 11/3/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency power test failed (would not transfer to emergency power) retest & check for proper operation. Re-inspection required 11/17/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators connected to an emergency or standby generator shall be tested for operation on emergency or standby power. Re-inspection required 10/13/2022