Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x All FAID devices to be functionality tested at completion of #3 MOD inspection. 10/28/2025
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) The counterweight hitch end has a spring that is broken in the hoistway that shall be replaced for the hoisting ropes to have an equal amount of tension. 11/18/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Fill smoke penetrations with approved fire caulking/materials. 10/28/2025
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x Main and lighting disconnects shall have proper labeling for function and feeder locations. 10/28/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Test rescue phone for all 3 units. Must be tested at the time of final modernization. 11/18/2025
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 x Reinstall handrail on steps going into machine room. 11/18/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Double outlet in the pit shall be GFCI protected or removed. 10/28/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Install missing duct covers. 10/28/2025
A17.1-2016 : Elevators 2.4 - Machine space 2.8.1 x Fill smoke penetrations with approved fire rated caulking. 11/18/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x Outlets shall be GFCI protected. 11/18/2025
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage There is no signage for Firefighters Operation by the phase I and phase II key switches. Obtain the correct signage from the building code addition that this elevator was designed to meet. 9/16/2024
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage There is no signage for Firefighters Operation by the phase I and phase I key switches. Obtain the correct signage from the building cade addition that this elevator was designed to meet. 11/18/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x All call stations in lobby must be permanently mounted. 10/28/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Written maintenance control program shall be kept on site for each elevator. 12/18/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.5 Code Data Plate There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1984), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. 9/16/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.5 Code Data Plate There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1984), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. 11/18/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods On the top of the elevator cab, the cab steadier bushings have degraded and require replacement. 11/18/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x A proper fire extinguisher shall be provided. 10/28/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts The counterweight hitch end has a spring that is broken in the hoistway that shall be replaced for the hoisting ropes to have an equal amount of tension. 11/18/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts On the top of the elevator cab, the cab steadier bushings have degraded and require replacement. 11/18/2025
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.6.4.13 x 3rd floor door upthrusts shall be adjusted for proper clearance. 10/28/2025