Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 Yes No Machine room lighting needs to be checked. 11/18/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Yes No Pit lighting needs to be checked. 11/18/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 Yes No Seal all penetrations in hoistway. 11/18/2025
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 Yes No Reinstall handrail on steps going into machine room. 11/18/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No Written maintenance control program shall be kept on site for each elevator. 12/18/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.5 Code Data Plate No No There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1984), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. 11/18/2025
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No There is no signage for Firefighters Operation by the phase I and phase II key switches. Obtain the correct signage from the building code addition that this elevator was designed to meet. 11/18/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.5 Code Data Plate No No There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A!&.1 1984), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. 11/18/2025
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No There is no signage for Firefighters Operation by the phase I and phase I key switches. Obtain the correct signage from the building code addition that this elevator was designed to meet. 11/18/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test Yes No All call stations in lobby must be permanently mounted. 11/18/2025