| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate |  |  | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1984), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. |  | 
                
                    | MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage |  |  | There is no signage for Firefighters Operation by the phase I and phase II key switches. Obtain the correct signage from the building code addition that this elevator was designed to meet. |  | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate |  |  | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1984) as used for all inspections. Provide a proper plate on the front of the controller or machine disconnect. |  | 
                
                    | MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage |  |  | There is no signage for Firefighters Operation by the phase I and phase I key switches. Obtain the correct signage from the building cade addition that this elevator was designed to meet. |  | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) |  |  | Written maintenance control program shall be kept on site for each elevator. | 12/18/2020 | 
                
                    | MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x |  | Governor rope is undersized, has rouging and irregular wear, needs to be replaced. Re-inspection required | 9/28/2023 |