Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No The car door restrictor shall be operational. 11/25/2019
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Install an anti-spin device on the hoist ropes. 11/25/2019
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Hoist ropes are rouged and have reached minimum diameter in several areas. Replacement of the hoist ropes is required. 11/25/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No The cab lighting shall be properly guarded. 12/15/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Replace the worn counterweight rollers. 12/15/2019
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean and dry. 12/15/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Replace the worn pick-up rollers at the 5th & 6th floor. 12/15/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display current operating certificate in machine room. 12/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 12/2/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No All smoke detectors need to be tested 10/15/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 Yes No Machine room shall be self closing and self locking 10/15/2021
MO Minimum : Elevators (H) - Machine Rooms (H)3 Yes No Grating in machine deck floor shall be fastened down or covered and fastened 10/15/2021
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Yes No Fire extinguisher in machine room needs replacing or servicing 10/15/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone in car shall work with failure indication and have battery backup for modem on phone line 10/15/2021
A17.1-2016 : Elevators 2.14 - Code data plate 8.7.1.8 Yes No Install code data plate containing all altered equipment code references to be installed on controller 10/15/2021
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.10.2.2.5(b) Yes No Runby signage shall be posted in pit 10/15/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) No No Smoke detector in the elevator machine room shall flash the in car fire hat 10/20/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency communication inoperable. Re-inspection required 2/14/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Test incomplete due to water in pit, safeties must be set. Re-inspection required 2/14/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Provide existing phone to work. 10/4/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) Yes No Sump pump in the pit is not working, repair/replace as needed. 10/4/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Remove water from the pit. 9/29/2025
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.1 No No Door knob to access the machine room is damaged, replace. 9/29/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Repair inoperative emergency phone 9/29/2025
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 2.14.7 No No Cab lighting shall be protected 9/29/2025
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 2.14.7 No No Two lamps are required. Lamps shall operate independently of each other. 9/29/2025
MO Minimum : Elevators (I) - Pits (I)1 No No Pit shall be kept dry and clear of debris 9/29/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Provide current year tested fire extinguisher in the elevator machine room. 9/29/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 No No Provide feeder location on the main line disconnect, in the elevator machine room.NEC620 9/29/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 No No Provide feeder location on the 110v. disconnect in the elevator machine room.NEC620 9/29/2025
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.1 No No Provide code compliant means to access secondary level in the elevator machine room. 9/29/2025
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 2.14.7 No No Cab lighting shall be wiring shall meet the NEC 10/23/2025
MO Minimum : Elevators (I) - Pits (I)1 No No Remove standing water from the elevator pit. 10/23/2025
MO Minimum : Elevators (I) - Pits (I)1 No No Pit shall be kept clean and dry. Sump not working. 10/23/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 No No Provide feeder location on the main line disconnect, in the elevator machine room.NEC620 10/23/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 No No Provide feeder location on the 110v. disconnect in the elevator machine room.NEC620 10/23/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Emergency light fixture lens is broken 10/23/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Hoist ropes and sheave are covered in grease. Ropes need cleaned 10/23/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Car lights need wired properly 10/23/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Phone does not dial. No phone line 10/23/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Fire extinguisher shall be kept up to date. 10/23/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Fire extinguisher shall be kept up to date 10/23/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Car lights needs wired properly per NEC 10/23/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 No No Provide feeder location on the 110v. disconnect in the elevator machine room.NEC620 10/23/2025