MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
All smoke detectors need to be tested
|
10/15/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test incomplete due to water in pit, safeties must be set. Re-inspection required
|
2/14/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone in car shall work with failure indication and have battery backup for modem on phone line
|
10/15/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication inoperable. Re-inspection required
|
2/14/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
The cab lighting shall be properly guarded.
|
12/15/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
12/2/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
The car door restrictor shall be operational.
|
11/25/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
x
|
|
Machine room shall be self closing and self locking
|
10/15/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)3
|
x
|
|
Grating in machine deck floor shall be fastened down or covered and fastened
|
10/15/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit shall be kept clean and dry.
|
12/15/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept dry and clear of debris
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove standing water from the elevator pit.
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Install an anti-spin device on the hoist ropes.
|
11/25/2019
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Hoist ropes are rouged and have reached minimum diameter in several areas. Replacement of the hoist ropes is required.
|
11/25/2019
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7
|
|
|
Cab lighting shall be protected
|
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7
|
|
|
Two lamps are required. Lamps shall operate independently of each other.
|
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7
|
|
|
Cab lighting shall be wiring shall meet the NEC
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
x
|
|
Sump pump in the pit is not working, repair/replace as needed.
|
10/4/2024
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection)
|
|
|
Smoke detector in the elevator machine room shall flash the in car fire hat
|
10/20/2021
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.1
|
|
|
Provide code compliant means to access secondary level in the elevator machine room.
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.1
|
|
|
Door knob to access the machine room is damaged, replace.
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
|
|
Provide feeder location on the main line disconnect, in the elevator machine room.NEC620
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
|
|
Provide feeder location on the 110v. disconnect in the elevator machine room.NEC620
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current operating certificate in machine room.
|
12/1/2020
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.10.2.2.5(b)
|
x
|
|
Runby signage shall be posted in pit
|
10/15/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
Replace the worn pick-up rollers at the 5th & 6th floor.
|
12/15/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
Replace the worn counterweight rollers.
|
12/15/2019
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
Fire extinguisher in machine room needs replacing or servicing
|
10/15/2021
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Provide current year tested fire extinguisher in the elevator machine room.
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair inoperative emergency phone
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide existing phone to work.
|
10/4/2024
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Remove water from the pit.
|
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.7.1.8
|
x
|
|
Install code data plate containing all altered equipment code references to be installed on controller
|
10/15/2021
|