Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x All smoke detectors need to be tested 10/15/2021
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 2.14.7 Cab lighting shall be protected
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 2.14.7 Cab lighting shall be wiring shall meet the NEC
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current operating certificate in machine room. 12/1/2020
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.1 Door knob to access the machine room is damaged, replace.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency communication inoperable. Re-inspection required 2/14/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 12/2/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone in car shall work with failure indication and have battery backup for modem on phone line 10/15/2021
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x Fire extinguisher in machine room needs replacing or servicing 10/15/2021
MO Minimum : Elevators (H) - Machine Rooms (H)3 x Grating in machine deck floor shall be fastened down or covered and fastened 10/15/2021
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Hoist ropes are rouged and have reached minimum diameter in several areas. Replacement of the hoist ropes is required. 11/25/2019
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Install an anti-spin device on the hoist ropes. 11/25/2019
A17.1-2016 : Elevators 2.14 - Code data plate 8.7.1.8 x Install code data plate containing all altered equipment code references to be installed on controller 10/15/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 x Machine room shall be self closing and self locking 10/15/2021
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept dry and clear of debris
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.1 Provide code compliant means to access secondary level in the elevator machine room.
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Provide current year tested fire extinguisher in the elevator machine room.
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Provide existing phone to work. 10/4/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Provide feeder location on the 110v. disconnect in the elevator machine room.NEC620
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Provide feeder location on the main line disconnect, in the elevator machine room.NEC620
MO Minimum : Elevators (I) - Pits (I)1 Remove standing water from the elevator pit.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Remove water from the pit.
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair inoperative emergency phone
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Replace the worn counterweight rollers. 12/15/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Replace the worn pick-up rollers at the 5th & 6th floor. 12/15/2019
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.10.2.2.5(b) x Runby signage shall be posted in pit 10/15/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) Smoke detector in the elevator machine room shall flash the in car fire hat 10/20/2021
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Sump pump in the pit is not working, repair/replace as needed. 10/4/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete due to water in pit, safeties must be set. Re-inspection required 2/14/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting The cab lighting shall be properly guarded. 12/15/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x The car door restrictor shall be operational. 11/25/2019
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. 12/15/2019
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 2.14.7 Two lamps are required. Lamps shall operate independently of each other.