Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(b)(1) Electric Elevators Placed out of Service x x Car failed safety test. Governor cable pulled thru jaws and failed to set safeties. Car was red tagged until repaired and retested.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 8.11.2.1.2(o) x Clean and adjust elevator machine brake.