Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x A17.1 2016 8.6.4.19.6 There are no fire alarm initiating devices within the vicinity of the elevator to initiate fire service phase 1 operations.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Position indicating device on the control operating panel is not functioning properly. Repair or replace.