Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting x Cab lighting breaker not labeled and could not be found by mechanic. Location info shall be labeled in machine room. 8/1/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting x Cab lighting breaker not labeled and could not be found by mechanic. Location info shall be labeled in machine room. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. 12/4/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting x Cab lighting breaker not labeled and could not be found by mechanic. Location info shall be labeled in machim room. (ligting tested by alternate means)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers x A current tested & tagged ABC type fire extinguisher shall be provided in the machine room, convenient to the access door. 8/1/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records x Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. 12/4/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers x A current tested & tagged ABC type fire extinguisher shall be provided in the machine room, convenient to the access door. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. 12/4/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(c) On-Site Maintenance Records (Other Records) x Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly. Note: last updated 7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers x Machine room fire extinguisher shall have currently monthly/annual test tag. No extinguisher in room or immediately adjacent to door.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly. 12/4/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance x The hydraulic tank drip pan has an excessive amount of oil, it shall be cleaned. 9/6/2023
MO Minimum : Elevators (H) - Machine Rooms (H)8 x Machine room lighting shall be guarded against breakage. 8/1/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x Possible single bottom jack. If the installation is determined to be a single bottom type, the jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. Documentation shall be kept on-site at all time and shall be provided to the state. No documentation provided in the machine room. Jack head is 1972 Otis Cast Head. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. 12/4/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x Possible single bottom jack. If the installation is determined to be a single bottom type, the jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. Documentation shall be kept on-site at all time and shall be provided to the state. 9/6/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x Possible single bottom jack. If the installation is determined to be a single bottom type, the jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. Documentation shall be kept on-site at all time and shall be provided to the state. Jack head is 1972 Otis "Cast Head" and no documentation has been provided. Corrective action shall be taken immediately. 8/1/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x Possible single bottom jack. If the installation is determined to be a single bottom type, the jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. Documentation shall be kept on-site at all time and shall be provided to the state. 9/6/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x x Failed 15min leak-down test.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x Need to determine if this unit has a single bottom jack. It it does it is required to be replace or a governor with safties installed or a plunger gripper installed on the unit. Ref: 8.6.5.8, A17.2-5.11 memorandum from the State of Missouri, effective May 30, 2007. No documentation in the machine room. Jack is 1973 OTIS CAST HEAD.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/4/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/4/2025