Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not working. 12/6/2023
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure Exposed wiring on top of car 10/20/2020
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) FFS Phase II hold not working 10/20/2020
MO Minimum : Elevators (H) - Machine Rooms (H)1 Keep access to machine room stairs clear, and unobstructed. 12/20/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Provide a self closing, self locking mechanism for machine room door. 12/20/2023
MO Minimum : Elevators (F) - Electrical Switches (F)2 x The car does not reach the upper final limit switch. The runby is insufficient, shorten the ropes. 6/9/2021