Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)2 Yes No > 2.8.2 Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 10/5/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 10/5/2023
MO Minimum : Elevators (I) - Pits (I)1 Yes No All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. Pit has 4 to 6 inches of water in it. 9/7/2023
MO Minimum : Elevators (I) - Pits (I)1 Yes No Clean the pit. Remove rust from pit equipment, repair/replace as needed. Apply rust preventative treatment to all pit steel. Pit shall be kept clean and dry, investigate/repair water leak. 8/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly. 5/12/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No Elevator is equipped with an overspeed valve and category 5 testing is due on or before the next annual inspection. 5/12/2026
MO Minimum : Elevators (H) - Machine Rooms (H)2 Yes No Machine room door shall be self-closing & self-locking. 8/7/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Yes No Machine room door shall be self-closing and self-locking.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Yes No Machine room door shall be self-closing and self-locking. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. 5/12/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. Yes No Per the MO AHJ, this elevator has been confirmed to have a single bottom jack. The jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. If the jack is replaced, documentation shall be available on-site at all time and shall be provided to the state. 9/7/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Yes No Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered. 9/7/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Yes No Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered. (Multi-year violation) 8/7/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Yes No Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. 5/12/2026
MO Minimum : Elevators (I) - Pits (I)1 Yes No Pit shall be kept dry. Clean Pit. Remove rust from pit equipment , repair/replace as needed, apply rust prevention treatment to all pit steel. Pit shall be kept dry investigate/repair water leak Pit has 4-6" water/oil.
MO Minimum : Elevators (I) - Pits (I)1 Yes No Pit shall be kept dry. Clean pit; remove rust from pit equipment, repair/replace as needed, apply rust prevention treatment to all pit steel. Pit shall be kept dry, investigate/repair source of water leak. Pit has 4-6" of water/oil. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. 5/12/2026
MO Minimum : Elevators (I) - Pits (I)1 Yes No Pit sump not working. Repair/replace as needed. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. 5/12/2026
MO Minimum : Elevators (I) - Pits (I)1 Yes No Pit sump pump not working. Repair or replace as needed. 8/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance Yes No The hydraulic tank drip pan has an excessive amount of oil, it shall be cleaned. 8/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Yes No The hydraulic tank drip pan has an excessive amount of oil, it shall be cleaned. 9/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No The in car emergency light shall be operational. 9/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No The in car emergency light shall be operational. (Multi-year violation) 8/7/2024