Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 10/5/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate x A current MO State operating certificate shall be posted in the elevator equipment room in a non-combustible frame with a clear protective vision plate over it. (2020 displayed, muli-year violation))
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/4/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 10/5/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/4/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers x An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 8/1/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers x An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. 12/4/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Compliant/Required documentation shall be kept in equipment room (neat/organized), including MCP, wiring diagrams, PM Log, callback log, oil log, & evacuation procedures. Fire service log to be recorded monthly. 12/4/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records x Compliant/Required documentation shall be kept in equipment room (neat/organized), including MCP, wiring diagrams, PM Log, callback log, oil log, & evacuation procedures. Fire service log to be recorded monthly. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. 12/4/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements x Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly. (last documented update 7/2022, must be updated on every visit)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers x Machine room fire extinguisher shall have current monthly/annual test tag. No extinuisher in room or immideiately adjcent to door.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x Need to determine if this unit is a single bottom jack. If it is required to be replaced or a governor with safeties installed or a plunger gripper installed on the unit. Ref: 8.6.5.8, A17.2-5.11 Memorandum form the State of Missouri, effective May 30, 2007. No documentation in the machine room. Jack head is 1972 OTIS CAST HEAD (multi-year violation)
MO Minimum : Elevators (I) - Pits (I)1 x Pit shall be kept clean & dry. Remove debris and mud. Remove rust from pit equipment. Repair/replace as needed and apply rust prevention treatment to all pit steel. Investigate/repair source of leak. 8/1/2024
MO Minimum : Elevators (I) - Pits (I)1 x Pit shall be kept clean & dry. Remove debris and mud. Remove rust from pit equipment. Repair/replace as needed and apply rust prevention treatment to all pit steel. Investigate/repair source of leak. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. 12/4/2025
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) x Pit shall be kept clean/dry. Remove debris and mud, remove rust from pit equipment, repair/replace as needed, apply tust prevention treatment to all pit steel, investigate/repair water leak.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x Possible single bottom jack. If the installation is determined to be a single bottom type, the jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. Documentation shall be kept on-site at all time and shall be provided to the state. 9/5/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x Possible single bottom jack. If the installation is determined to be a single bottom type, the jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. Documentation shall be kept on-site at all time and shall be provided to the state. No documentation in the machine room. Jack head is 1972 Otis Cast Head. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. 12/4/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x Possible single bottom jack. If the installation is determined to be a single bottom type, the jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. Documentation shall be kept on-site at all time and shall be provided to the state. Note: Jack head is 1972 Otis "Cast Head". 8/1/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance x The hydraulic tank drip pan has an excessive amount of oil, it shall be cleaned. 8/1/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection x The hydraulic tank drip pan has an excessive amount of oil, it shall be cleaned. 9/5/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency light shall be operational. 9/5/2023