ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.11.2.1.5(b)
|
x
|
|
1) Runby before counterweight strikes buffer is 2 inches. Minimum is 6 inches. Suspension ropes need to be shorten. Ref: 8.11.2.1.5(b)
|
1/28/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.3.3.3 Runby & Clearances After Reroping or shortening
|
x
|
|
The elevator car when traveling in the up direction activates the buffer switch before the top direction limit. The current counterweight measurement is 4”. The hoistway ropes shall be shortened to 6” counterweight clearance or the direction limit shall be adjusted.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
2) Lighting in the machine room shall be not less than ten (10) foot-candles at floor level. Light above elevator machine not working. Ref: (H) 5
|
1/8/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
1) Emergency operation communication shall be maintained. Apparently the phone system on authorized personnel side has a problem. Ref: 8.6.4.15 This shall be addressed ASAP.
|
5/25/2021
|