MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
1) Lighting in the machine room shall be not less than ten (10) foot-candles at floor level. Light above elevator machine not working. And bulbs burnt out in secoundary over governor. Ref: (H) 5
|
1/8/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
1) Emergency operation communication shall be maintained. Apparently the phone system on authorized personnel side has a problem. Ref: 8.6.4.15 This shall be addressed ASAP.
|
5/25/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
2/28/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Inspection is incomplete. The following testing items shall be tested: Set the safeties and obtain a slide measurement, door pressure shall be tested, and fire service shall be tested.
|
2/28/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The emergency car lighting is not operational.The fixture shall be repaired to operate. Reinspection required.
|
10/17/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
The hoistway door to sill gap is excessive and shall be readjusted to the maximum of 3/8”.
|
10/5/2023
|