Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Inspection is incomplete. The following testing items shall be tested: Set the safeties and obtain a slide measurement, door pressure shall be tested, and fire service shall be tested. 2/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems The hoistway door to sill gap is excessive and shall be readjusted to the maximum of 3/8”. 10/5/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency car lighting is not operational.The fixture shall be repaired to operate. Reinspection required. 10/17/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x 1) Emergency operation communication shall be maintained. Apparently the phone system on authorized personnel side has a problem. Ref: 8.6.4.15 This shall be addressed ASAP. 5/25/2021
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) 1) Lighting in the machine room shall be not less than ten (10) foot-candles at floor level. Light above elevator machine not working. And bulbs burnt out in secoundary over governor. Ref: (H) 5 1/8/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 2/28/2022