Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 Remove water/oil slurry from pit
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load every 5 years.
MO Minimum : Elevators (I) - Pits (I)1 All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. The sump pump is not working. There is a water/oil mixture in the pit.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work. 9/12/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Telephone in car doesn't work. Phone line dead to elevator controller. 10/1/2020