Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) Yes No Car door restrictor does not function 5/16/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) Yes No Car door restrictor does not function. 11/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.16 - Rated load, platform area, and data plate 2.16.3.1 Capacity Plates No No Install 2500 LBS Capacity plate inside the elevator. The existing capacity plate does not correspond with crosshead data plate. 6/21/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.7.2 Periodic Test Record (Test Tags) No No Install and date period test tag 11/13/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.16 - Rated load, platform area, and data plate 2.16.3.1 Capacity Plates No No Install capacity plate inside the elevator "2000 lbs Capacity" 11/13/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.2.1.3(r) No No Install covers on 4x4 electrical gangboxes at top of hoistway 2/22/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.2.1.3(r) No No Install covers on conduit pullboxes located near top of hoistway. 11/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.27 - Crosshead data plate 8.11.2.1.3(k) No No Install suspension rope data tag to ropes 2/22/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 No No Machine room access door shall be self-closing 11/13/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.9 - Guarding of exposed auxiliary equipment 2.10.1 No No Provide guarding of machine drive sheave and hoist ropes. 11/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.8 - Door closing force 2.13.4.2.3 Yes No REDUCE DOOR TORQUE TO LESS THAN 30lbs 10/10/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.11.1 No No Test and log firefighter operation monthly 11/19/2021