                        MO Minimum : Elevators
                     | 
                    
                        (G) - Maintenance, Repair and Replacements
                     | 
                    
                        8.6.1.6 General Maintenance Methods
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed.
                     | 
                    
                        1/9/2024
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        (G) - Maintenance, Repair and Replacements
                     | 
                    
                        (G)1 Maintenance, Repair and Replacements
                     | 
                    
                     | 
                    
                     | 
                    
                        Sump hole is filled with oil, remove. Check sump pump operations, replace if not functioning.
                     | 
                    
                        
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        (H) - Machine Rooms
                     | 
                    
                        (H)4
                     | 
                    
                     | 
                    
                     | 
                    
                        The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed.
                     | 
                    
                        5/29/2024
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        (H) - Machine Rooms
                     | 
                    
                        (H)4
                     | 
                    
                     | 
                    
                     | 
                    
                        Remove all the non elevator related items from the elevator machine room. No storage allowed.
                     | 
                    
                        
                     | 
                
                
                    | 
                        A17.1-1996 : Elevators
                     | 
                    
                        1.18 - Restricted opening of car or hoistway doors
                     | 
                    
                        1001.2(a)(18)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection required.
                     | 
                    
                        5/29/2019
                     | 
                
                
                    | 
                        A17.1-1996 : Elevators
                     | 
                    
                        3.18 - Car frame and stiles
                     | 
                    
                        1200.4
                     | 
                    
                     | 
                    
                     | 
                    
                        Bottom right car sling guide is broken.
                     | 
                    
                        3/18/2021
                     | 
                
                
                    | 
                        A17.1-1996 : Elevators
                     | 
                    
                        5.1 - Pit access, lighting, stop switch, and condition
                     | 
                    
                        106.1e Illumination of Pits
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor.
                     | 
                    
                        10/29/2018
                     |