A17.1-1996 : Elevators
|
3.18 - Car frame and stiles
|
1200.4
|
|
|
Bottom right car sling guide is broken.
|
3/18/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed.
|
5/29/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
x
|
|
The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed.
|
1/9/2024
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
x
|
|
The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor.
|
10/29/2018
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
x
|
|
The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection required.
|
5/29/2019
|