Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Sump hole is filled with oil, remove. Check sump pump operations, replace if not functioning.
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. 5/29/2024
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Remove all the non elevator related items from the elevator machine room. No storage allowed.
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) Yes No The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection required. 5/29/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Yes No The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. 10/29/2018
A17.1-1996 : Elevators 3.18 - Car frame and stiles 1200.4 No No Bottom right car sling guide is broken. 3/18/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Yes No The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. 1/9/2024